Switchgear
MV switchgear
Panel arrangements for incoming, outgoing, bus-coupler and metering functions. Coordinate ratings, protection, interlocks and cable interfaces.

Application & selection
Define the complete panel schedule.
Key information for configuration review
- Single-line diagram and panel schedule
- Rated voltage, busbar current, short-circuit level
- Protection philosophy and relay brand
- Control voltage
Technical overviewStart with the
Start with the
right specification.
Use this selection reference to prepare your project brief.
Reference values are not a model datasheet. Availability, standards and test coverage require confirmation for the offered equipment.
Download project sheets ↓Selection reference +
| Rated voltage | 12, 24, 36 kV |
|---|---|
| Busbar current | 630 to 3,150 A |
| Short-time withstand | 20 to 31.5 kA 3 s |
| Panel types | Metal-clad withdrawable (e.g. KYN28 type at 12 kV), air-insulated fixed; incomer, feeder, bus-coupler, metering, capacitor |
| Loss of service continuity | LSC2B (metal-clad) where specified |
| Internal arc | IAC AFLR where specified |
Testing topics to confirm +
Confirm the applicable requirements, available reports and agreed test scope with the proposed manufacturer.
| Routine tests | Dielectric test, main circuit resistance, mechanical operation, wiring and functional tests |
|---|---|
| Type tests (per design) | Full IEC 62271-200 type test series including internal arc where specified |
Project document package +
- Model-specific datasheet and approved drawings
- Applicable test reports and their coverage
- Inspection, packing and delivery requirements
Project resourcesBring your next project
Bring your next project
into focus.
Explore the equipment guide and prepare your requirements with our fillable project sheets.